Product Description
1. Scope of Application
GTR-841 integrated measuring and control device for power plant, substation automation system, provide a complete measurement and control functions. It can be achieved in two groups of
current voltage measurement. It can be used for plant (station) transformer, low voltage inlet line (400V),
measurement and control.
2. Functional Configuration and Characteristics
Functional Configuration Table
Classification | Function Name |
Measuring and control function | 19~33 circuits remote binary input acquisition |
18 circuit remote control, 22 circuit programmable binary output |
2 sets amount of current and voltage, among 8 circuits of voltage, 12 circuits of current, a total of 20 circuits of ac input |
P,Q,IA,IB,IC,Ua,Ub,Uc,f,COSφ |
Clock Synchronization | can realize GPS clock synchronization, timing |
Communication | Ethernet, RS232/485 communication interface |
Main Features
a. 4U standard aluminum chassis, combination of plug-in structure, after the plug case, each functional module design alone, strong and weak electricity are completely separated, strong anti-interference ability, convenient field maintenance;
b. Multi-CPU intelligent card design, binary input and output plug-ins to achieve real-time complete self-test; can be detected in each relay coil;
c. Based on CANBUS bus link between plug-ins, reduce the connection between plug-ins, bad real time detection;
d. Double 32-bit computer system, the redundant system; protection function using the 32 bits floating-point DSP processor produced by the Dezhou Instrument Company, program and data in the chip operation; fast operation speed, high reliability;
e. Man-machine interface, network communication and other management functions by Philips Company produced 32 bits ARM MCU, fast speed, big storage capacity on-chip, strong ability of network interface;
f. 16 bits AD sampling, high measuring precision; weekly wave 48 points sampling, strong harmonic processing capability;
g. Protection module using computer assisted graphical interface design is convenient for the secondary development and functional modification of the products, flexible and quick
engineering design;
h. Use 192*64 monochrome graphic LCD, Chinese interface menu; the flexibility to choose double Ethernet and dual 485 interface;
i. Can save at least 500 recent incidents report and operation reports;
j. Man-machine management module using real-time multitasking operating system, interface and network tasks such as good real-time;
k. Can store 10 sets of protection setting value, double value zone self-test and mutual combination, setting change safety and convenient.
l. Based on electric power industry standard DL / T667-1999 (IEC 60870-5-103) standard
communication protocol, and convenient with microcomputer monitoring or protect management computer network communication.
3. Technical Index
3.1 Rated Data
a. Rated DC voltage: 220V (110V orders indicate) allowable deviation +15%,-20%
b. Rated AC data: phase voltage 100/ √3 V
Zero-sequence voltage 100V
AC current 5A (1A orders indicate)
Rated frequency 50Hz (60Hz orders indicate)
c. Thermal Stability:
AC voltage circuit: long time operation 1.4Un
AC current circuit: long time operation 2In
10s 20In
1s 40In
3.2 Consumption
a. AC voltage circuit: phase≤0.5VA;
b. AC current circuit: when In=5A ,phase ≤1VA;when In=1A, phase≤0.5VA;
c. Protection power supply circuit: when in normal work, ≤10W; in protection action, ≤15W.
3.3 Environment Condition
a. Environment temperature:
Work: -25ºC~+55ºC
Storage: -25ºC ~ +70ºC , relative humidity of not more than 80%, the ambient air does not
contain acidic, alkaline or other corrosive and explosive gases prevent rain, snow indoor;
the limit without applying excitation volume, device is not irreversible change in
appearance, device can work normally after the temperature recovery.
b. Relative humidity: Most of the wet mean monthly maximum relative humidity is 90%, and the monthly mean minimum temperature is 25ºC and the surface without gel. When the maximum temperature is +40ºC, the average maximum humidity is not more than 50%.
c. Atmospheric pressure:80kPa~110kPa(Altitude < 2km)
Installation Picture of Protection Relay
Address:
A4 Building, Lugu International Industrial Park, No. 229, Tongzipo West Road, High-Tech Development Zone, Changsha, Hunan, China
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics
Management System Certification:
ISO 9001, ISO 9000
Company Introduction:
Changsha Guotong Electrical Technology Co. Ltd. Is a specialized corporate integrated R&AMP;D, design, production and sales of microcomputer protection and integrated automation systems fitting for hydropower, power, pump and thermal power stations etc.
As a rapid developing corporation, Guotong has been optimizing its products. Nowadays, GT8000 series has been attached most importance, which can be applied to transformer substation, hydropower station, switch station, pumping station, power plant, cement factories, railway, chemical, environmental protection, steel, coal and mine substation etc. Of 110kv and below. Moreover, Guotong Electric successfully constructed multi-level marketing networks around domestic and abroad, which is covered a number of countries and regions, such as the Middle East, East Europe, South Africa, Southeast Asia, and South America.
Guotong adheres to the spirit of market oriented and innovation as strength and keep technological leadership, transforming science and technology into reality. Therefore, Guotong has received a number of related intellectual property rights and internationally recognized.